I live on the 14th floor of a 30 story apartment building and so far, I've been bleeding my radiators myself.

This usually worked and after bleeding I had a fully functioning radiator, 100% filled with water.

However, last time I tried bleeding, it would only fill up to 25% of its volume, it's like there's no pressure in the circuit.

Am I doing something wrong?

you are viewing a single comment's thread
view the rest of the comments
[-] nous@programming.dev 65 points 2 months ago

A water central heating system is a closed loop system that is under pressure. This means the water in it is circulated around and around the system and is cut off from other water supplies under normal operation. Naturally, slow leaks happen and gas can enter the system in various ways so occasionally this needs to be released from the system. Any gas in the system naturally collects at the highest points along the path - which tend to be the radiators.

When you bleed a radiator you are opening the system to the outside and hopefully where the gas has accumulated. Since the system is under pressure it forces the gas out of the system to equalize the pressure with the outside. This will cause the pressure of the system to drop and eventually it will stop.

However there should be a control valve somewhere, typically on/near the boiler that connects the central heating system up to the mains water supply. You can open this valve to cause water to flow into the central heating system and pressurize it and really this should be done every time you bleed the radiator a significant amount.

In apartments though you might find that you are on a building wide circuit, or you might have one isolated for your apartment. If you have a boiler in your apartment then you are likely on a closed system and should be able to equalize the pressure yourself. If it is building wide you need to talk with your building manager.

Note that you should not need to bleed your radiators that often. Once every several years should be more than enough. If you are doing it frequently then you likely have a large leak in your system and likely want to get someone to check that out.

[-] ODuffer@lemmy.world 12 points 2 months ago

Great answer, there should also be a pressure gauge somewhere on the boiler. As mentioned, this is really for your building manager though.

this post was submitted on 16 Sep 2024
55 points (98.2% liked)

No Stupid Questions

35868 readers
387 users here now

No such thing. Ask away!

!nostupidquestions is a community dedicated to being helpful and answering each others' questions on various topics.

The rules for posting and commenting, besides the rules defined here for lemmy.world, are as follows:

Rules (interactive)


Rule 1- All posts must be legitimate questions. All post titles must include a question.

All posts must be legitimate questions, and all post titles must include a question. Questions that are joke or trolling questions, memes, song lyrics as title, etc. are not allowed here. See Rule 6 for all exceptions.



Rule 2- Your question subject cannot be illegal or NSFW material.

Your question subject cannot be illegal or NSFW material. You will be warned first, banned second.



Rule 3- Do not seek mental, medical and professional help here.

Do not seek mental, medical and professional help here. Breaking this rule will not get you or your post removed, but it will put you at risk, and possibly in danger.



Rule 4- No self promotion or upvote-farming of any kind.

That's it.



Rule 5- No baiting or sealioning or promoting an agenda.

Questions which, instead of being of an innocuous nature, are specifically intended (based on reports and in the opinion of our crack moderation team) to bait users into ideological wars on charged political topics will be removed and the authors warned - or banned - depending on severity.



Rule 6- Regarding META posts and joke questions.

Provided it is about the community itself, you may post non-question posts using the [META] tag on your post title.

On fridays, you are allowed to post meme and troll questions, on the condition that it's in text format only, and conforms with our other rules. These posts MUST include the [NSQ Friday] tag in their title.

If you post a serious question on friday and are looking only for legitimate answers, then please include the [Serious] tag on your post. Irrelevant replies will then be removed by moderators.



Rule 7- You can't intentionally annoy, mock, or harass other members.

If you intentionally annoy, mock, harass, or discriminate against any individual member, you will be removed.

Likewise, if you are a member, sympathiser or a resemblant of a movement that is known to largely hate, mock, discriminate against, and/or want to take lives of a group of people, and you were provably vocal about your hate, then you will be banned on sight.



Rule 8- All comments should try to stay relevant to their parent content.



Rule 9- Reposts from other platforms are not allowed.

Let everyone have their own content.



Rule 10- Majority of bots aren't allowed to participate here.



Credits

Our breathtaking icon was bestowed upon us by @Cevilia!

The greatest banner of all time: by @TheOneWithTheHair!

founded 1 year ago
MODERATORS